Our editorial team weighed ChampionPowerEquipment's published specifications and how it stacks up against similar products in the generators category. What stands out: Dual Fuel, Propane Hose Included, High Starting Watts for AC Units, and GFCI-Protected Outlets. Where it falls short: Heavy at 209 lbs and 74dB Noise Level. That puts it at 8.1/10 on our WG Score – an excellent, well-rounded option.
Propane line size for a generator depends on kW and run length: a 7-8 kW unit needs 3/4-inch pipe for runs up to 165 feet.
Propane line size chart by generator kW and run length
| Generator size | 3/4 in. pipe | 1 in. pipe | 1-1/4 in. pipe |
|---|---|---|---|
| 7-8 kW | 165 ft | 570 ft | Not listed |
| 11 kW | 70 ft | 255 ft | 1,000 ft |
| 16 kW | 25 ft | 130 ft | 540 ft |
| 20-22 kW | 15 ft | 115 ft | 480 ft |
Every figure is the maximum straight-pipe run from Generac’s standby propane vapor table, as quoted by InspectApedia. It assumes a second-stage regulator and sizing at 100% load. Treat it as a single-source guide: other brands and models differ, so the manual and local code decide the final size.
How to calculate the right propane line size
- Find the generator’s rated propane consumption at full load in the manual, in gal/hr or cu ft/hr.
- Convert it to BTU/hr: gal/hr x 91,500, or cu ft/hr x 2,500.
- Measure the pipe run from the regulator to the generator and add the equivalent length of every fitting.
- Read the pipe size from the manual or code table (NFPA 54 or IFGC) for that BTU/hr and length. Capacity tables are commonly built on about 0.5 in. w.c. of pressure drop.
In this example, a 20 kW unit burns about 3.85 gal/hr at full load (InspectApedia figure; use your own unit’s number). That is 3.85 x 91,500 = 352,275 BTU/hr, or about 141 cu ft/hr (352,275 / 2,500).
Say the run is 40 ft with 4 elbows, and in this example the code table counts each elbow as 2 ft. The effective length is 40 + (4 x 2) = 48 ft. The 20-22 kW row allows only 15 ft of 3/4 in. pipe, so it fails. It allows 115 ft of 1 in. pipe, so 1 in. works.
What changes the pipe size: pressure, fittings and regulators
- Pressure system: A low-pressure line delivers about 11 in. w.c. to the generator, and propane vapor delivery is 10-12 in. w.c. A 2 psi line carries more gas through the same pipe, so it allows smaller pipe. It needs its own 2 psi table and a second-stage regulator at the generator.
- Fittings: Elbows, tees and valves add equivalent length. The chart above covers straight pipe only.
- Full-load sizing: Size for the generator’s maximum rating, not the load you expect to run. A line sized for half load starves the engine at full output.
- Two-stage regulation: The first stage at the tank drops tank pressure. The second stage near the generator sets final delivery pressure, and the chart assumes it.
Portable generators: hose, 20 lb tank and small lines
A portable generator uses a short flexible hose and a tank, not fixed pipe. Use the hose and regulator the manufacturer specifies. A barbecue-style hose and 20 lb tank run only the units whose manual lists them, because a tank must vaporize propane as fast as the engine burns it, and small tanks fall behind at high load.
- If the manual lists a larger tank or a tank size minimum, that requirement overrides any hose or pipe size.
- For long runs between tank and generator, one small-unit Winco manual cited in a search snippet calls 1/2 to 5/8 in. line adequate up to 300 ft from the first-stage to the low-pressure regulator. Confirm this in your own manual before copying it.
- Generators need vapor withdrawal. Liquid draw from a tank is wrong for the engine unless the manual states otherwise.
Standby units have their own tank minimums. Generac, for example, specifies a minimum 250 gal LP tank, and vertical tanks need at least 1,050 lb capacity.
Pipe materials, permits and checking pressure under load
Common materials are black iron, CSST, copper and polyethylene for underground runs, and local code decides which are allowed. Connect the generator through the manufacturer’s flexible connector, never CSST directly, and do not bend that connector. Fit a full-flow shutoff valve and a sediment trap where required.
Fixed gas piping needs a licensed plumber or propane supplier, a permit and inspection under NFPA 54, NFPA 58 and local code. Do not skip the pressure test.
Leak and pressure checks
- Brush soapy water on every joint and look for bubbles. Never use a flame, because propane is heavier than air and pools low.
- Put a manometer on the line at the generator and run it at full load.
- Confirm pressure stays in the manual’s range, about 10-12 in. w.c. for propane vapor. A drop below it points to an undersized line, a restricted fitting or a regulator problem.
Keep the generator outdoors and away from openings, and use CO alarms indoors.
Our Top Picks
Ready to shop? These are the top-rated options from our related roundup, Best Propane Generator For Home of 2026.
Westinghouse WGen11500TFc 14500 Peak Watt Tri-Fuel Portable Generator with Remote Start & CO Sensor
Westinghouse WGen9500DF Dual Fuel Portable Generator 12500 Peak Watts Remote Start Transfer Switch Ready
Champion 11,500W Dual Fuel Portable Generator Electric Start CO Shield Home Backup Power
As an Amazon Associate we earn from qualifying purchases. Product prices and availability are accurate as of the date/time indicated.
Frequently Asked Questions
Can a tankless water heater share the generator’s propane line?
Only if you add both appliances’ BTU/hr and size the pipe for the combined total. A line sized for the generator alone starves both appliances when they run together.
Can I use a propane-sized line for natural gas?
No. Natural gas is delivered at roughly 3.5-7 in. w.c. and needs its own sizing table. Propane pipe sizes do not carry over to a natural gas conversion.
Will a bigger pipe fix a regulator that frosts over under load?
No. Frost means the tank cannot vaporize propane as fast as the engine draws it. Cut the load or add tank capacity; pipe diameter does not change that.
Do I need to resize the line if I buy a bigger generator?
Yes. Pipe size is set by the generator’s full-load BTU/hr, so recalculate with the new unit’s rated consumption before reusing the old pipe.
{“@context”: “https://schema.org”, “@type”: “FAQPage”, “mainEntity”: [{“@type”: “Question”, “name”: “Can a tankless water heater share the generator’s propane line?”, “acceptedAnswer”: {“@type”: “Answer”, “text”: “Only if you add both appliances’ BTU/hr and size the pipe for the combined total. A line sized for the generator alone starves both appliances when they run together.”}}, {“@type”: “Question”, “name”: “Can I use a propane-sized line for natural gas?”, “acceptedAnswer”: {“@type”: “Answer”, “text”: “No. Natural gas is delivered at roughly 3.5-7 in. w.c. and needs its own sizing table. Propane pipe sizes do not carry over to a natural gas conversion.”}}, {“@type”: “Question”, “name”: “Will a bigger pipe fix a regulator that frosts over under load?”, “acceptedAnswer”: {“@type”: “Answer”, “text”: “No. Frost means the tank cannot vaporize propane as fast as the engine draws it. Cut the load or add tank capacity; pipe diameter does not change that.”}}, {“@type”: “Question”, “name”: “Do I need to resize the line if I buy a bigger generator?”, “acceptedAnswer”: {“@type”: “Answer”, “text”: “Yes. Pipe size is set by the generator’s full-load BTU/hr, so recalculate with the new unit’s rated consumption before reusing the old pipe.”}}]}